I have a 14 Amp Ryobi miter saw. In the manual it has a table for required AWG by Cord Length and Amps. For 100’ and 12.1-16.0 Amps it just has a dash indicating there is no suitable AWG extension cable for this length and amp combination.

However, protoolreviews indicates 12 AWG is sufficient for 15 Amps and 100’, but 10 AWG would be safer. https://www.protoolreviews.com/extension-cord-size-chart-wire-gauge-amps/

Is protoolreviews correct and I can get away with a 10 AWG, 100’ extension cord for my 14 Amp tool just fine?

I know if something goes wrong it will likely be on me as Ryobi will point out I didn’t follow the manual.

  • Hazdaz@lemmy.world
    link
    fedilink
    English
    arrow-up
    1
    arrow-down
    1
    ·
    11 months ago

    Run it for a few days at the expected use amount and keep an eye on the heat of the cord but also the outlet and plug. I do have to say that 100’ is a lot. No outlets closer than that to you?